The basic version of XIOS UC consists of the Main board (MC), extendable by up to 5 extension modules (MA) and an Expander Board MD1 or MD2.

I/O capacity of the Main Board:

Analogue/digital input Digital output Hall pick-up Sensor supply
11x 2x, max. 4A 2x 2x (5 or 12 VDC configurable)

The XIOS Expander boards MD1 or MD2 offer options for connecting further Extension Boards (MA).

I/O capacity of the Expander Board MD1:

Analogue/digital input Digital input Digital output Inductive pick-up Sensor supply Additional slots
8x 2x 2x, max. 4A 2x 1x (5 or 12 VDC configurable) 6x board MA

Board MD2 is required for the XIOSGenSet and XIOSCHP applications.

I/O capacity of the Expander Board MD2: all possibilities of MD1 and in addition

Digital Input Analogue input AVR output Relay output Addtional slots
4x, isolated 6x AC voltage (3x bus und 3x generator)
4x AC phase current, max. 5 A
1x 1x 3x board MA

  Each of the Extension Modules provides 2 (if isolated), 4 or 8 (if input-only) I/O channels, resulting in a great variety of
  configuration options:

Module type Function
 A2 4x analogue or digital output, monitored, 0...5 VDC (11 mA), 0...24 mA
digital output, max. 1 A PWM controlled (0...100 %)
 A3 4x analogue or digital input, 0...5/10/36 VDC, 0...24 mA
temperature input Pt 1000, Pt 200, Pt 100, Ni 1000, NTC
2x sensor supply (5/12 VDC configurable, 50 mA or VBAT)
 A4 2x analogue or digital input, electrically isolated, 0...5/10/36 VDC, 0...24 mA
temperature input Pt 1000, Pt 200, Pt 100, Ni 1000, NTC
2x sensor supply (5 VDC, 50 mA)
 A5 2x analogue or digital output, electrically isolated, 0...5 VDC (2.5 mA), 0...24 mA
digital output: 60 VDC/40 VAC, 400 mA static, optional: 400 VDC/280 VAC, 100 mA
 A6 2x analogue or digital output, electrically isolated, monitored, 0...5 VDC (10 mA), 0...24 mA
 A7 6x digital input, 9...36 VDC
 A8 up to 4x digital output, high or low-side, current read back for control-loop applications, thermal shutdown
 
 A1 2x thermocouple amplifier, electrically isolated, (J/K/E/R/S/B/N), configurable gain and offset
 A9 1x H bridge output, up to 8 A static current, current read back for control-loop applications

We use cookies on our website. However, non-essential cookies (e.g. tracking cookies) are only set if you consent to their use. We point out that in connection with these cookies, your personal data may be transferred to US service providers and merged with other personal data. In the case of data transfers to the USA, there is a risk that this data will be accessed by US authorities without notification and without any legal remedy. With your consent, you also agree to this data transfers to the USA. For more information on the cookies we use, their purposes and storage periods, please refer to our privacy notice at: www.heinzmann.com/en/privacy-policy.